ACCEPTANCE TESTS HYDRO GENERATOR HM HYDRO 140 MVA



TFA for Mediciones ALSER SRL



SCOPE OF WORK

  • Stator core ELCID Test.
  • Stator windings insulation resistance and polarization index test IEEE 43-2013.
  • Stator windings resistance test IEEE 118-1978
  • Stator winding DC hi-pot test 1.7*(2*Un + 1000 V) according to IEEE- 115-2009 , NEMA MG1 and IEC 60034.
  • Stator windings RTD insulation resistance and Hi-Pot test.